New CAT Equipment

MX350 Controller

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.

Get a Quote

    Fabick Cat needs this information to contact you about our products and services. You may unsubscribe from communications at any time. For more information, please review our Privacy Policy.

    Benefits

    The MX350 microprocessor

    is standard with the entire CTE product family

    Graphical Control Panel

    interface provides local control and access to system information. Automation FlexLogic� with interlocking and programmable logic control
    • Controller Specifications
      Communications Interface - Optional
      Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)
      Control Power
      120 VAC
      Delay NeutralTransition Time Delays (DT,DW)
      0-10 minutes
      Delay Transfer to Nonpreferred Source (W)
      0-5 minutes
      Delay for Engine Cool Down (U)
      0-60 minutes
      Load Control Relay Contacts (1)
      rated for 10A @ 24VDC or 120VAC
      Load Control Relay Contacts (2)
      0-259 minutes
      Operating Temperature Ambient
      (-20˚C to 50˚C)
      Overfrequency Dropout for Source 1 and Source 2
      50.1 - 63 Hz
      Overfrequency Restore for Source 1 and Source 2
      50 - 62.9 Hz
      Overvoltage Dropout for Source 1 and Source 2
      105 - 110% of nominal
      Overvoltage Restore for Source 1 and Source 2
      103 - 108% of nominal
      Source Sensing
      120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)
      Storage Temperature
      (-40˚C - 90˚C )
      Underfrequency Dropout for Source 1 and Source 2
      45 - 59.9 Hz
      Underfrequency Restore for Source 1 and Source 2
      45 - 59.5 Hz
      Undervoltage Dropout for Source 1 and Source 2
      75-99% of nominal
      Undervoltage Restore for Source 1 and Source 2
      85-100% of nominal
      Voltage Unbalance for Restore for Source 1 and Source 2
      4 to 19% of nominal
      Voltage Unbalance on Dropout for Source 1 and Source 2
      5 to 20% of nominal
    • Technical Summary
      Rating Range
      Switch Dependent
      Switch Type
      Application Dependent
      Transfer Type
      Application Dependent
    Status LEDS for:
    • Transfer Inhibit
    • Active Alarms
    • Source 1 and 2 Availablity
    • Source 1 and 2 Connected
    • Time Delay Active
    Graphical Display:
    • Color graphical display with USB Calibration/programming port and Embedded Help
    • Displays 256 time-tagged events with 1 ms resolution
    • Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
    • Provided detailed outage,test,and diagnostic reports
    Ranges of Controls / Metering:
    • Programmable generator exerciser
    • Synchroscope
    • Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
    • Source 1 and Source 2 In-phase monitor
    • Neutral, Engine Start, and Engine stop time delay timers
    Testing and Certification
    • Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
    • Tested in accordance with:
      IEC 60068-2-30
      IEC 60068-2-1
      IEC 60068-2-2
      IEC 60255-22-1
      IEC 60255-22-2
      IEC 60255-22-3
      IEC 60255-22-4
      IEC 60255-22-5
      IEC 60255-22-6
      IEC 60255-25
      IEC 60529; IP54 (front),IP20(back)
      IEC 61000-4-11
    • Quality System:
      Manufactured under an ISO 9001 Registered Program
    Option Package A:
    • Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
    • Expanded diagnostics, high-speed 256 event capture, 365 days
    • Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
    • Full function ATS control with full sensing and control capabilities
    • Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)
    Option Package B:
    • Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
    • Ten (10) customer programmable digital and ten (10)analog alarms.
    • Includes Option Package A features, plus
    • Auto Load Shed with voltage, frequency and kW triggers.
    • Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.
    Option Package C:
    • Includes Option B features, plus
    • Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)
    Option Package D:
    • Customized user control logic
    • Includes Option Package C features, plus
    • Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)
    Option Package M:
    • Configuration for Manual Operation only (Non-Automatic)