New CAT Equipment

D80 GC Generator Set

80 ekW Diesel Generator Set

Producing reliable power of 80 ekW at 60 Hz, our D80 GC diesel generator sets are designed to meet ISO 8528-5 transient response requirements. All D80 GC generator sets meet EPA Stationary Emergency (Tier 3) emissions standards.

Get a Quote

    Fabick Cat needs this information to contact you about our products and services. You may unsubscribe from communications at any time. For more information, please review our Privacy Policy.

    Benefits

    Saves up to 17% Installed Space

    Requires less space for installation; leaves more room for your on-going operations

    Spare Parts 98% Fulfillment within 24 hours

    World's best product support network ensures spare parts are readily available for maintenance and service needs

    Reliability tested for 500 Hours

    Ensures you can count on emergency power when it is needed
    • Engine Specifications
      Aspiration
      Turbocharged
      Bore
      4.1 in
      Compression Ratio
      16.7:1
      Displacement
      269 in³
      Engine Model
      C4.4, In-line 4, 4-cycle diesel
      Fuel System
      Common Rail
      Governor Type
      Mechanical, ADEMA4
      Stroke
      5 in
    • Generator Set Dimensions
      Dry Weight - Genset (maximum)
      950 lb
      Height - Maximum
      52.9 in
      Length - Maximum
      82.6 in
      Width - Maximum
      43.3 in
    • Generator Set Specifications
      Duty Cycle
      Standby
      Emissions/Fuel Strategy
      U.S. EPA Cert., Tier 3
      Frequency
      60 Hz
      Maximum Rating
      80 ekW
      Minimum Rating
      80 ekW
      Speed
      1800 rpm
      Voltage
      208 to 600 Volts
    Air Inlet System
    • Air cleaner; light duty with disposable element
    • Air cleaner
    Cooling System
    • Radiator and cooling fan with guards
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
    • Coolant drain line with valve
    Control Panel
    • GCCP 1.2 Control panel
    Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
    Fuel System
    • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
    Generator
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Voltage regulator (single phase sensing)
    • IP23 Protection
    • Segregated low voltage (AC/DC) wiring panel
    • 12 Leads
    • Tower panel, IP22, bottom cable entry
    Governing System
    • Mechanical and electrical governing system - model dependent
    Lube System
    • Lubricating oil
    • Oil drain line with valve
    Mounting System
    • Includes lifting provision and drag points
    • Termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
    Starting/Charging System
    • Batteries
    • 24V battery with rack and cables
    General
    • Engine and alternator pre-paint, Caterpillar yellow
    Alternator System
    • 3 Phase sensing
    • Anti-condensation heater
    • R Frame auxilliary winding
    • Permanent magnet excitation (PMG)
    Circuit breakers
    • Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
    Cooling System
    • Low coolant level shutdown
    • Coolant heater
    • Low coolant temperature alarm
    Control Panel Options
    • Earth fault (2 wire only)
    • Overload shutdown via breaker
    • Earth leakage (2 wire only)
    • Volt free contacts
    • Panel mounted audible alarm
    • Battery charger
    • GCCP 1.2 Control panel
    • Control panel heater
    • Voltage adjust potentiometer
    • Emergency stop with key
    • Speed adjust potentiometer
    Enclosures
    • Sound attenuated Level 2 enclosure
    Fuel System
    • High fuel level alarm
    • Open set narrow tankbase
    • Low fuel level alarm
    • Bunded fuel tank
    • Low fuel level shutdown
    • Compact skidbase for open set
    • Skidbase for CALG enclosure sets
    Global Certifications
    • Certification for CIS
    Mounting Options
    • Battery removal
    • Industrial silencer
    • Electronic governor
    • External single point lift - enclosure
    • Silencer installation kit
    Special Packing/Inspectons for Shipment
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    General - Accessories / Miscellaneous
    • Stone guards/rad trans flange
    • Packing case - canopied set
    • Packing case - compact set