New CAT Equipment

D200 GC Generator Set

200 ekW Diesel Generator Set

Producing reliable power of 200 ekW at 60 Hz, our D200 GC diesel generator set is designed to meet ISO 8528-5 transient response requirements.

Get a Quote

    Fabick Cat needs this information to contact you about our products and services. You may unsubscribe from communications at any time. For more information, please review our Privacy Policy.

    Benefits

    Saves up to 18% Installed Space

    Requires less space for installation; leaves more room for your on-going operations

    Reliability tested for 500 Hours

    Ensures you can count on emergency power when it is needed

    Spare Parts 98% Fulfillment within 24 hours

    World's best product support network ensures spare parts are readily available for maintenance and service needs
    • Engine Specifications
      Aspiration
      Turbocharged, Air to Air Aftercooled
      Bore
      4.1 in
      Compression Ratio
      16.7:1
      Displacement
      428 in³
      Engine Model
      C7.1 I-6, 4-Cycle Diesel
      Fuel System
      Electronic, Common Rail
      Governor Type
      ADEMA4
      Stroke
      5.31 in
    • Generator Set Dimensions
      Dry Weight - Genset (maximum)
      3917 lb
      Height - Maximum
      58.7 in
      Length - Maximum
      103.7 in
      Width - Maximum
      51.2 in
    • Generator Set Specifications
      Duty Cycle
      Standby
      Emissions/Fuel Strategy
      U.S. EPA Cert., Tier 3
      Frequency
      60 Hz
      Maximum Rating
      200 ekW
      Minimum Rating
      200 ekW
      Speed
      1800 rpm
      Voltage
      208 to 600 Volts
    Air Inlet System
    • Air cleaner; light duty with disposable element
    Control Panels
    • GCCP 1.2 Control panel
    Cooling System
    • Coolant drain line with valves
    • Radiator and cooling fan with guards
    • Caterpillar extended life coolant
    • Fan drive, battery charging alternator drive
    Generator and Generator Attachments
    • Segregated low voltage (AC/DC) wiring panel
    • Voltage regulator (single phase sensing)
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Tower panel, IP22, bottom cable entry
    • 12 Leads
    • IP23 Protection
    Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
    Fuel System
    • Standard open set fuel tank/base supplied
    • Base, formed steel with single wall integral 24-hour fuel tank
    Lube System
    • Oil drain line with valve
    • Lubricating oil
    Mounting System
    • Captive linear vibration isolators between base and engine-generator
    • Includes lifting provision and drag points
    • Termination points for coolant and lube oil drain lines
    Starting / Charging System
    • 24V battery with rack and cables
    Governing System
    • Mechanical and electrical governing system - model dependent
    General
    • Engine and alternator pre-paint, Caterpillar yellow
    Alternator System
    • Quatrature droop king
    • Permanent magnet excitation (PMG)
    • R Frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
    • Alternator removal
    • Anti-condensation heater
    • 3 Phase sensing
    • Optional LC Frame alternator with coastal insulation protection
    Circuit breakers
    • Padlockable breaker device
    • 4 Pole 250A, 400A and 630A Circuit breakers
    Control Panel Options
    • Earth leakage (2 wire only)
    • Panel mounted audible alarm
    • Speed adjust potentiometer
    • Overload shutdown via breaker
    • Emergency stop with key
    • Earth fault (2 wire only)
    • Control panel heater
    • Battery charger
    • Speed adjust contacts
    • Volt free contacts
    Control System
    • Volt free contacts for generator set running
    • GCCP 1.2
    • Volt free contacts for common alarm
    • Static battery charger
    Cooling System
    • Low coolant temperature
    • Coolant heater
    • Low coolant level shutdown
    Enclosures
    • Sound attenuated level 2 enclosure
    Mounting Options
    • Silencer installation kit
    • Battery removal
    • Electronic governor
    • Industrial silencer removal
    • Residential silencer
    Fuel Systems
    • Open set narrow tankbase
    • Low fuel level shutdown
    • Low fuel level alarm
    • Compact skidbase for open sets
    • DEFRA bunded fuel tank
    • High fuel level alarm
    • Skidbase for CALG enclosure sets
    Test Reports
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    General
    • Stone guards/radiator trans flange
    Global Certifications
    • Certification for CIS
    Power Termination
    • Circuit breaker, IEC, 4 pole
    Accessories / Miscellaneous
    • Packing case - canopied set
    • Packing case - compact set