New CAT Equipment

D100 GC Generator Set

100 ekW Diesel Generator Set

Producing reliable power of 100 ekW at 60 Hz, our Cat® C4.4 D100 GC diesel generator sets are designed to meet ISO 8528-5 transient response requirements complying to U.S. EPA Tier 3 emissions standards.

Get a Quote

Benefits

Saves up to 12% Installed Space

Requires less space for installation; leaves more room for your on-going operations

Reliability tested for 500 Hours

Ensures you can count on emergency power when it is needed

Spare Parts 98% Fulfillment within 24 hours

World's best product support network ensures spare parts are readily available for maintenance and service needs
  • Engine Specifications
    Aspiration
    Turbocharged
    Bore
    4.1 in
    Compression Ratio
    16.7:1
    Displacement
    269 in³
    Engine Model
    C4.4, In-line 4, 4-cycle diesel
    Fuel System
    Common Rail
    Governor Type
    Mechanical, ADEM™A4
    Stroke
    5 in
  • Generator Set Dimensions
    Dry Weight - Genset (maximum)
    2222 lb
    Height - Maximum
    52.9 in
    Length - Maximum
    82.6 in
    Width - Maximum
    43.3 in
  • Generator Set Specifications
    Duty Cycle
    Standby
    Emissions/Fuel Strategy
    U.S. EPA Tier 3 Certified
    Frequency
    60 Hz
    Speed
    1800 rpm
    Standby Rating
    100 ekW
    Voltage
    208 to 600 Volts
Air Inlet System
  • Air cleaner; light duty with disposable element
  • Air cleaner
Cooling System
  • Coolant drain line with valve
  • Radiator and cooling fan with guards
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
Control Panel
  • GCCP 1.2 Control panel
Exhaust System
  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
Fuel System
  • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
Generator
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • IP23 Protection
  • Tower panel, IP22, bottom cable entry
  • 12 Leads
  • Voltage regulator (single phase sensing)
  • Segregated low voltage (AC/DC) wiring panel
Governing System
  • Mechanical and electrical governing system - model dependent
Lube System
  • Lubricating oil
  • Oil drain line with valve
Mounting System
  • Termination points for coolant and lube oil drain lines
  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provision and drag points
Starting/Charging System
  • Batteries
  • 24V battery with rack and cables
General
  • Engine and alternator pre-paint, Caterpillar yellow
Alternator System
  • Anti-condensation heater
  • 3 phase sensing
  • Permanent magnet excitation (PMG)
  • R Frame auxilliary winding
  • Quadrature droop kit
Circuit breakers
  • Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
Cooling System
  • Coolant heater
  • Low coolant temperature alarm
  • Low coolant level shutdown
Control Panel Options
  • Earth fault (2 wire only)
  • Control panel heater
  • GCCP 1.2 Control panel
  • Volt free contacts
  • Emergency stop with key
  • Voltage adjust potentiometer
  • Overload shutdown via breaker
  • Panel mounted audible alarm
  • Battery charger
  • Earth leakage (2 wire only)
  • Speed adjust potentiometer
Enclosures
  • Sound attenuated Level 2 enclosure
Fuel System
  • Low fuel level alarm
  • Bunded fuel tank
  • Low fuel level shutdown
  • High fuel level alarm
Mounting Options
  • Battery removal
  • Electronic governor
  • Industrial silencer
  • External single point lift - enclosure
  • Silencer installation kit
Special Packing/Inspectons for Shipment
  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor
General - Accessories / Miscellaneous
  • Packing case - canopied set
  • Packing case - compact set
  • Stone guards/rad trans flange