    Technical Summary

    Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
    Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
    Application LV and MV ( 208V - 38 kV

    Generator Protective Devices

    ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51

    Utility Protective Devices

    ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

    Environmental Parameters

    Certifications IBS, CBC, UBC & OSHPD Certified
    Control Panel Enclosure NEMA 1 or NEMA 3R, Freestanding Construction
    Operating Temperature 0 degrees to 50 degrees C
    Storage Temperature -20 degrees C to +60 degrees C
    Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70