Engine Specifications
Aspiration
Turbocharged and aftercooledBore
5.7 inDisplacement
1959 in³Engine Model
Vee-12, 4-stroke-Cycle-DieselFuel System
MEUIGovernor Type
ElectronicStroke
6.38 in -
Generator Set Dimensions
Height
65.6 inLength
162.8 in/4271 mm (minimum), 175.3 in/4452 mm (maximum)Weight - Estimated
15721 lbWidth
60.2 in -
Generator Set Specifications
Emissions/Fuel Strategy
EPA Tier IIIFrequency
60hzMaximum Rating
940 ekW (1175 kVA)Minimum Rating
730 ekW (913 kVA)Speed
1800 rpm -
Generator Specifications
Excitation
Permanent magnetIP Rating
23Insulation
Class HNumber of Bearings
2 roller bearingsNumber of Leads
6Number of Poles
4Voltage Regulator
CDVR
AIR INLET SYSTEM
- Separate circuit after-cooled (SCAC)
- Turbocharger, jacket water cooled
- Turbocharger inlet, 152 mm (6 in) OD straight connection
CONTROL SYSTEM
- If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
- Electronic diagnostics and fault logging
- Engine Protection Mode for extended ambient conditions
- Electronic fuel/air ratio control
COOLING SYSTEM
- Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
- Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
- SCAC pump, gear driven
- Jacket water pump, gear driven
- Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
- Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
- 4 Bolt ANSI Flange Connection
- Jacket water HEX without Sea water pump Connection: 2.5" hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
- Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
- SCAC and JW shunt tanks for maintaining proper Pump inlet pressures
EXHAUST SYSTEM
- Water-cooled exhaust manifold & turbocharger
- 4 Bolt 130 mm (5.12 in) diameter flanged outlet
FLYWHEELS & FLYWHEEL HOUSINGS
- Flywheel Housing, SAE No. 0
- Flywheel, 18 inch, 136 teeth
- SAE standard rotation
FUEL SYSTEM
- Duplex Fuel Filters, Spin-on, RH service
- Fuel connections size: Supply JIC 37 Deg -10 (7/8-14), Return JIC 37 Deg -8 (3/4-16)
- Plate-type fuel cooler installed behind Aftercooler Shunt Tank
- Fuel transfer pump, gear driven
- Manual fuel priming pump
GENERATORS AND GENERATOR ATTACHMENTS
- SR5 form wound
- 2 roller bearings
- Permanent magnet excitation
- 4 pole, 6 leads, Series Star connected
- Caterpillar's Digital Voltage Regulator (CDVR)
- Marine Class H insulation, Class F temperature rise
- Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
- Anti-condensation space heaters (2 elements - 240 VAC, 1000 Watts
- IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
- System IV insulation for harsh environment protection
LUBE SYSTEM
- Simplex oil filters, RH service
- Deep sump oil pan
- RH service oil filler locations
- RH service dipstick
- Oil pump, gear driven
MOUNTING SYSTEM
- Formed C-channel rails, 300mm (11.81in) height
- Six shipped loose combined helical spring/rubber
- isolators for installation below package base
GENERAL
- Front Damper guard
- Common electrical bondng point on HEX and KEEL cooled engines
ALARM AND PROTECTION
- Remote panels
- MCS Controller
- Power analyzer module
- Oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors
EXHAUST SYSTEM
- Dry Elbows
- Flexible Fitting
- Flange
- Muffler
- Muffler Spark Arresting
- Rain Cap
AIR INLET SYSTEM
- Air Inlet Cleaner
- Closed Crankcase Ventilation
- Air inlet adapter
CHARGING SYSTEM
- Battery Chargers, Charging Alternators
CONTROL SYSTEM
- Load Sharing Attachment
FUEL SYSTEM
- Water Separator
LUBE SYSTEM
- Duplex Oil Filters, Sump Pump
PROTECTION SYSTEM
- Fuel and Oil Shielding
STARTING SYSTEM
- Electric Starting Motors - Single 24 Volt
- Air Starting Motor
- Dual Starting Motors (Electric and Air)
- Air Start Accessories
- Starting Aids - JW Heaters
- Battery Sets - 24 Volt - Dry