72 - 100 ekW Diesel Generator Set

Producing reliable power from 72 to 100 ekW at 60 Hz, our C4.4 diesel generator sets designed to ISO 8528-5 transient response requirements. All C4.4 generator sets meet EPA Stationary Emergency (Tier 3) emissions standards.

Get a Quote

Benefits

Suitable for Harsh & Testing Environments

Optimised for 5% Lower Fuel Consumption

Longer run times between fuel fills; reduced operating costs

Reliability tested for minimum 500 Hours

Ensures you can count on emergency power when it is needed
  • Engine Specifications
    Aspiration
    Turbocharged
    Bore
    4.1 in
    Compression Ratio
    16.2:1, 17.25:1, 18.2:1 or 18.3:1
    Displacement
    268.5 in³
    Engine Model
    Cat® C4.4
    Fuel System
    Direct Injection or Common Rail
    Governor Type
    Mechanical
    Stroke
    5 in
  • Generator Set Dimensions
    Height - Maximum
    53.6 in
    Length - Maximum
    75.8 in
    Width - Maximum
    44.1 in
  • Generator Set Specifications
    Duty Cycle
    Standby, Prime
    Emissions/Fuel Strategy
    U.S. EPA Cert., Tier 3
    Frequency
    60 Hz
    Maximum Rating
    100 ekW
    Minimum Rating
    72 ekW
    Speed
    1800 rpm
    Voltage
    110 to 480 Volts
Air Inlet System
  • Air cleaner; light duty with disposable element
Cooling System
  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
Control Panel
  • GCCP 1.3
Exhaust System
  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
Fuel System
  • Standard open set fuel tank/base supplied base, formed steel with single wall integral 8-hour fuel tank
Generator
  • Voltage regulator (single phase sensing)
  • 12 Leads
  • IP23 Protection
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Segregated low voltage (AC/DC) wiring panel
  • Tower panel, IP22, bottom cable entry
Governing System
  • Mechanical and electrical governing system - model dependent
Lube System
  • Oil drain line with valve
  • Lubricating oil
Mounting System
  • Termination points for coolant and lube oil drain lines
  • Includes lifting provision and drag points
  • Captive linear vibration isolators between base and engine-generator
Starting/Charging System
  • 24V battery with rack and cables
  • Batteries
General
  • Engine and alternator pre-paint, Caterpillar yellow
Alternator System
  • Permanent magnet excitation (PMG)
  • R Frame auxilliary winding
  • Anti-condensation heater
  • R Frame auxilliary winding
  • Quadrature droop kit
  • LC Frame alternator with coastal insulation protection
  • 3 phase sensing
Circuit breakers
  • Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
Cooling System
  • Low coolant level shutdown
  • Coolant heater
  • Low coolant temperature alarm
Control Panel Options
  • GCCP 1.3
  • Control panel heater
  • Earth leakage (2 wire only)
  • Panel mounted audible alarm
  • Volt free contacts
  • Emergency stop with key
  • Battery charger
  • Overload shutdown via breaker
  • Speed adjust potentiometer
  • Voltage adjust potentiometer
Enclosures
  • Sound attenuated Level 2 enclosure
  • Sound attenuated Level 1 (galv)
  • Rental pack - CAE rental option only
European Certifications
  • Upgrade to STD set for CE
Fuel System
  • Skidbase for CALG enclosure sets
  • Low fuel level alarm
  • Open set narrow tankbase
  • Low fuel level shutdown
  • Compact skidbase for open set
  • High fuel level alarm
  • Bunded fuel tank
Global Certifications
  • Certification for CIS
Mounting Options
  • Electronic governor
  • Industrial silencer
  • External single point lift - enclosure
  • Battery removal
  • Silencer installation kit
Special Packing/Inspectons for Shipment
  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor
General - Accessories / Miscellaneous
  • Packing case - compact set
  • Packing case - canopied set
  • Stone guards/rad trans flange