New CAT Equipment

C32 (60 Hz)

830 - 1250 ekW Diesel Generator Set

Producing reliable power from 830 to 1250 ekW at 60 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% block load. Generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certification.

Get a Quote

Benefits

Saves up to 8% installed space

Requires less space for installation

Weighs 28% less

Reduced amount of structural support required

Full Power up to 50°C Ambient

Provides full power even on hottest days of the year

G3 Class Load Acceptance

Learn more about the C32 (60 Hz)

Watch

  • Engine Specifications
    Aspiration
    TA
    Bore
    5.71 in
    Compression Ratio
    15.0:1
    Displacement
    1958.86 in³
    Engine Model
    C32 TA, V-12, 4-Stroke Water-Cooled Diesel
    Fuel System
    MEUI
    Governor Type
    AdemA4
    Stroke
    6.38 in
  • Generator Set Dimensions
    Dry Weight - Genset (maximum)
    16755 lb
    Dry Weight - Genset (minimum)
    14700 lb
    Height - Maximum
    86.4 in
    Height - Minimum
    85.1 in
    Length - Maximum
    172.7 in
    Length - Minimum
    164 in
    Width - Maximum
    87.7 in
    Width - Minimum
    66.3 in
  • Generator Set Specifications
    Duty Cycle
    Standby, Mission Critical, Prime, Continuous
    Emissions/Fuel Strategy
    Low Fuel, Tier 2 Nonroad Stds
    Frequency
    60 Hz
    Maximum Rating
    1250 ekW
    Minimum Rating
    830 ekW
    Speed
    1800 rpm
    Voltage
    220 to 4160 Volts
Air Inlet System
  • Single element canister type with service indicator
Control Panel
  • Warning shutdowns
  • GCCP 1.2
  • Digital Indicators
  • Communications
  • Control features
  • Programmable protective relaying functions
Cooling System
  • Caterpillar extended life coolant
  • ATAAC
  • Coolant drain line with valve
  • Low coolant level sensor
  • Fan and belt guards
  • Radiator fan and fan drive
Exhaust System
  • 203 mm (8 in) ID round flanged outlet
  • Exhaust manifold - dry
Fuel System
  • Fuel cooler
  • Fuel priming pump
  • Secondary fuel filters
  • Primary fuel filter with water separator
General
  • RH service
  • Caterpillar yellow with high gloss black rails & radiator
  • SAE standard rotation
  • Flywheel and flywheel housing-SAE
Generators and Attachments
  • Class H temperature rise at 40C ambient
  • 3 Phase brushless
  • Permanent magnet excitation (PMG)
  • Winding temperature detectors
  • Integrated voltage regulator (IVR)
  • Reactive droop
  • IEC standard hole pattern
  • NEMA Class H insulation
  • Busbar connections, top center mounted, top cable entry
  • Salient pole
  • 6 Lead
  • Internal excitation (IE)
Governing System
  • ADEM(tm) A4
Lube System
  • Gear type lube oil pump
  • Oil drain lines and valve
  • Fumes disposal
  • Lubricating oil
  • Integral lube Oil cooler
  • Oil filter, filler and dipstick
Mounting System
  • Rubber anti-vibration mounts
  • Rails - Engine/generator/radiator mounting
Power Termination
  • Busbar
Starting and Charging
  • 45 Amp Charging alternator
  • 24 Volt electric starting motor
  • Battery disconnect switch
  • Battery, rack and cables
Air Inlet System
  • Standard air cleaners
  • Heavy duty air cleaner
  • Dual element air cleaner
Circuit breakers
  • Shrouds
  • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
  • Center posts busbars
  • Enclosures - Control packaging
  • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
  • Circuit breaker wiring groups
  • Power connection covers
  • Cable supports
  • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
Control Panels
  • CAT ECS 200
Cooling System
  • High ambient radiator
  • Extended life coolant
  • Standard radiator
  • Radiator duct flange
  • Certified radiator
Enclosures
  • Premium sound attenuated enclosure
  • Cold weather bundle
  • Color options
  • DC lighting package
  • Sound attenuated enclosure
  • AC Panel, outlets and lights
  • Panel bracket
  • Enclosure fuel tank options
  • Enclosure louvers - fixed and motorized
Exhaust System
  • Elbow mounting kit
  • Mufflers
  • Guard and shield system
  • Flange and exhaust expanders
  • Flexible fittings
  • All C32 engines have 203 mm (8 in) exhaust outlets
  • Flanges
  • Exhaust through the wall kit
General
  • US aid emblem
  • Special paint
Generator and Attachments
  • Medium voltage optional generators
  • Low voltage optional generators
Lube System
  • Oil level regulator
  • Oil pan
  • Prelube manual sump pump
Mounting System
  • Spring type vibration isolators
  • IBC vibration isolators
  • Mounting base types
  • Standard package isolators
Power Connections
  • Center post busbars
  • Low voltage connection cables
  • Neutral grounding connection
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
Special Tests / Reports
  • Standard engine test
  • IBC seismic Certifications
  • PGS Test report @ 1.0 power factor
  • Custom generator TVA report
  • Generator test report
  • Standard genset Torsional Vibration Analysis (TVA) report
  • PGS Test report @ 0.8 power factor
  • CSA test and certification
  • OSHPD seismic Certifications
Starting / Charging
  • 10 Amp enclosure Battery charger
  • 35 Amp Battery charger
  • Space heater
  • Jacket water heater
  • Electric starting motor - Standard/heavy duty
  • Heavy duty starting system
  • 10 Amp Battery charger
  • 20 Amp Battery charger