The ATC-900 Controller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-900 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

Get a Quote

Benefits

The ATC-900 is a programmable microprocessorbased monitoring device for use on Cat� transfer switches

It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels

Frequency Measurement Accuracy
+/- 0.1 Hz
Frequency Measurement Range
40 Hz to 80 Hz
Frequency Measurements Of
Source 1 and Source 2
Input Control Voltage
120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Operating Humidity
Up to 90% Relative Humidity (non-condensing)
Operating Temperature Range
-20 to 70 degree C (-4 to +158 degree F)
Overfrequency Dropout Range
103 to 110% of Nominal System Frequency
Overfrequency Pickup Range
101% to (Dropout +1 Hz) of nominal system frequency
Underfrequency Dropout Range
90 to 97% of Nominal System Frequency
Underfrequency Pickup Range
(Dropout +1 Hz) to 99% of Nominal System Frequency
Undervoltage Dropout
Breaker Style 50 to 97% of Nominal System Voltage
Contactor Style - 78 to 97%
Undervoltage Pickup
(Dropout +2%) to 99% of Nominal System Voltage
Voltage Measurement Accuracy
+/-1% of full scale
Voltage Measurement Range
0 to 700 Vac
Voltage Measurements of Utility
Source 1, Source 2 and Load
(VAB, VBC, VCA for Three Phase System)
  • Ratings
    System Voltage Application
    120 to 600 Vac (50/60 Hz) (single or three phase)
  • Technical Summary
    Rating Range
    120 to 600V, single phase and three phase @ 50/60 Hz
    Switch Type
    Switch application dependent
    Transfer Type
    Switch application dependent