The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.

Get a Quote

    Fabick Cat needs this information to contact you about our products and services. You may unsubscribe from communications at any time. For more information, please review our Privacy Policy.

    Benefits

    The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller

    It is a Compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.

    • ATC Controller Specifications
      Applicable Testing
      UL-recognized component
      Meets intent of UL 991 & UL 1008
      Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
      Applicable Testing Continued
      1000-4-5, 1000-4-6, 1000-4-11
      CISPR 11, Class A
      FCC Part 15, Class A
      CSS 22.2-178
      Enclosure Compatibility
      NEMA 1, NEMA 3R and NEMA 12
      UV-resistant ATC-300+ faceplate
      Frequency Measurement Accuracy
      +/- 0.1 Hz
      Frequency Measurement Range
      40 Hz to 70 Hz
      Frequency Measurements Of
      Source 1 and Source 2
      Generator Start Relay
      5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
      Input Control Voltage
      65 to 145 Vac 50/60 hZ
      K1, K2 Relays

      10A, 1-3 hp @ 250 Vac

      10A@30 Vdc
      Operating Environment
      Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
      Operating Humidity
      0 to 95% relative humidity (noncondensing)
      Operating Temperature Range
      -20 to 70 degree C (-4 to +158 degree F)
      Overfrequency Dropout Range
      103 to 110% of the nominal system frequency
      Overfrequency Pickup Range
      101% to (dropout - 1 Hz) of the nominal system frequency
      Storage Temperature Range
      -30 to 85 degree C (-22 to +185 degree F)
      Underfrequency Dropout Range
      90 to 97% of the nominal system frequency
      Underfrequency Pickup Range
      (Dropout +1 Hz) to 99% of the nominal system frequency
      Undervoltage Dropout
      50% to 90% of nominal voltage
      Undervoltage Pickup
      (Dropout +2%) to 99% of the nominal system voltage
      Voltage Measurement Accuracy
      +/-2% of nominal input voltage
      Voltage Measurement Range
      0 to 790 VAC rms (50/60 Hz)
      Voltage Measurements of Utility
      Source 1 VAB Source 2 VAB
      Source 1 VAC Source 2 VBC
      Source 1 VCA Source 2 VCA
    • Technical Summary
      Rating Range
      120 to 600V, single phase and three phase @ 50/60 Hz
      Switch Type
      Switch application dependent
      Transfer Type